Skip to Main Content
Building Safety Journal Logo

Building Safety Journal - International Code Council

Main Menu

Menu

      • July, 2026 Articles
      • June, 2026 Articles
      • May, 2026 Articles
      • April, 2026 Articles
      • March, 2026 Articles
      • February, 2026 Articles
      • 2026 Articles
      • 2025 Articles
      • Deep Dives
      • Member News
      • Personal Perspectives
      • Quick Hits
      • Technical Topics
      • Press Releases
      • Sponsored Content
      • View All
      • Buildings, Construction, Architecture/Design
      • Fire, Wildland-Urban Interface
      • Plumbing, Mechanical, Fuel Gas, Pools/Spas
      • Energy, Solar, Green, Sustainability
      • Disaster Preparedness, Mitigation, Resiliency
  • Subscribe
    • ICC Family of Solutions
    • ICCSafe
    • myICC
    • Digital Codes
    • cdpACCESS
    • Store
    • Support

Join today!

Keep up-to-date on crucial industry news, innovative training and expert technical advice with a free subscription to the award-winning Building Safety Journal.

Subscribe

Sign In or Register Here

Provide your email address
Provide your password
Answer the math challenge
Please enter your e-mail address below. We will email you a link to reset your password.
Provide your email address
Answer the math challenge
To complete your registration, please verify your email address.
Answer the math challenge

We have emailed the address you provided. Please click the link in the email to confirm your email address.

Your account has been marked for password reset. Please change your password.
Provide your new password
Verify your new password
Answer the math challenge 7 minus four

Only registered ICC members have access to this article at this time.

Explore all the benefits that ICC Membership has to offer and become a member today to gain access to this exciting content.

If you're already an ICC member Sign In Now.

Can We Help?

  • Reset My Password
  • I Need More Help

Low‑Ambient Derating in Heat Pumps: Capacity Loss and Balance‑Point Calculation for Auxiliary Heat Requirements

The derating curve is not merely a performance characteristic, it is a design tool that shapes equipment selection, auxiliary heat sizing and overall system architecture.

August 3rd, 2026
by Sahil Mahajan, PE, P.Eng., CPD, LEED Green Associate
  • Deep Dives
  • Technical Topics

Heat pump technology has become a defining component of modern HVAC engineering in regions of the country where buildings are transitioning toward electrification and higher efficiency. Although all heat pumps rely on the vapor‑compression cycle, the way they reject heat – either to outdoor air or to a controlled water loop – creates substantial differences in performance, installation strategy and long‑term operating behavior.

These differences become even more pronounced when considering how air‑source heat pumps derate in low ambient temperatures, a factor that increasingly shapes system selection in cold‑climate regions.

Air-Cooled Versus Water-Cooled Heat Pumps, Explained

Air‑cooled heat pumps reject heat directly to the outdoor environment, which means their performance is tied to fluctuating ambient conditions. As outdoor temperatures rise, condensing pressures increase, reducing efficiency and raising compressor lift.

Water‑cooled heat pumps, by contrast, reject heat to a stable water loop maintained by a cooling tower, dry cooler or geothermal field. Because water has higher thermal conductivity and a narrower temperature range, these systems operate at lower condensing temperatures and achieve higher COP and EER values. This thermodynamic advantage explains why water‑cooled systems are often favored in large commercial buildings and high‑rise structures where mechanical room space is available and long‑term operating cost is a priority.

Installation Differences

The installation environment further differentiates the two systems. Air‑cooled units require outdoor placement with adequate airflow clearance, making them simple to install but more exposed to weather, debris, and acoustic concerns.

Water‑cooled systems require pumps, piping and a cooling water source, resulting in higher first cost but greater placement flexibility and quieter operation. Installation of this equipment in an indoor location, when feasible, also contributes to longer service life, while air‑cooled units typically experience more wear due to environmental exposure.

Performance Differences

A critical performance factor for air‑source heat pumps is capacity derating at low ambient temperatures. As outdoor air becomes colder, the amount of usable heat available decreases, forcing the heat pump to operate with a higher temperature lift between the outdoor coil and the indoor conditioned space. This reduces both heating capacity and efficiency. Frost accumulation on the outdoor coil triggers periodic defrost cycles, during which the system temporarily reverses operation, further reducing net heating output. Standard air‑source heat pumps may lose 10 to 20 percent of capacity at 35°F, 30 to 50 percent at 17°F, and more than half of their output as temperatures approach 0°F. Below 10°F, the derating curve bends sharply downward as the system approaches minimum allowable suction pressure and compressor operating limits.

By the Numbers

The following numerical example illustrates this behavior: A nominal 3-ton (36,000 Btu/h) heat pump rated at 47°F may deliver 31,000 Btu/h at 35°F, 27,000 Btu/h at 25°F, 22,000 Btu/h at 17°F, and only 17,000 Btu/h at 5°F. This corresponds to 100 percent, 86 percent, 75 percent, 61 percent, and 47 percent of nominal capacity, respectively. A cold‑climate inverter version of the same unit performs better, delivering 35,000 Btu/h at 35°F, 34,000 Btu/h at 25°F, 33,000 Btu/h at 17°F, and 30,000 Btu/h at 5°F which corresponds to 100 percent, 97 percent, 94 percent, 92 percent, and 83 percent of the heat pump capacity; still derating, but far more gradually.

See comparison charts for 3-ton (36,000 Btu/h) nominal and cold climate inverter air source heat pumps rated at 47ºF:

This derating behavior directly affects the building’s balance point, the temperature at which heat pump output equals the building’s heat loss.

Cold-Climate Engineering

Cold climate engineering requires careful consideration of envelope performance, emitter selection and system configuration. A tighter building envelope reduces the slope of the heat‑loss curve, lowering the balance point and reducing reliance on auxiliary heat.

Low‑temperature emitters such as radiant floors or oversized fan coils allow the heat pump to operate at lower supply temperatures, improving efficiency and reducing compressor lift. Reverse‑cycle defrost temporarily interrupts heating, and the frequency of these cycles increases as humidity rises and temperature falls. Demand‑based defrost strategies minimize unnecessary cycles and improve seasonal performance, which is especially important in humid continental climates.

System Selection

System selection in cold climates depends heavily on design temperature. In regions with design temperatures above 20°F, standard air‑source heat pumps are often sufficient. In climates with design temperatures between 0°F and 20°F, cold‑climate inverter heat pumps are preferred, with auxiliary heat expected during the coldest hours. In regions where design temperatures fall below 0°F, water‑source or geothermal systems become increasingly attractive because they avoid low‑ambient derating entirely. Hybrid systems that combine a heat pump with a boiler or furnace can also optimize performance by allowing the heat pump to operate in its efficient range while the auxiliary system handles extreme conditions.

Derating Curve Key Takeaways

Ultimately, the derating curve is not merely a performance characteristic. It is a design tool that shapes equipment selection, auxiliary heat sizing and overall system architecture.

Air‑cooled systems offer simplicity and lower first cost, making them suitable for residential and light commercial applications.

Water‑cooled systems deliver superior efficiency, quieter operation and longer lifespan, aligning with the needs of large commercial buildings and district energy systems. In cold climates, the impact of low‑ambient derating often becomes the deciding factor, pushing designers toward water‑source or geothermal solutions that maintain stable capacity regardless of outdoor temperature. Understanding these relationships allows engineers to design systems that balance efficiency, reliability and long‑term operating cost.

About the Author
Sahil Mahajan, PE, P.Eng., CPD, LEED Green Associate
Sahil Mahajan, PE, P.Eng., CPD, LEED Green Associate, has a Master of Science in Mechanical Engineering and is currently working at KEA Engineers in Iselin, New Jersey, as the Plumbing and Fire Protection Department Head. He has nearly 20 years of experience in HVAC, plumbing, and fire protection design and is a licensed Professional Engineer in the United States and Canada.
Submissions
Check out upcoming BSJ topics and send us articles for consideration:
Or send by email

Want to advertise in the BSJ?
Click Here

Share on Facebook
Facebook
Tweet about this on Twitter
Twitter
Share on LinkedIn
Linkedin

  • CSAO Building Officials Digital ICC Ad June 2026
  • edu an con ad
  • CodeEarnFrameSave 270
  • 26 26137 INTL Essential Fire Saftey BSJ Animated WAD FINAL
  • 26 25989 MTS Nash BSJ 270x270 WAD FINAL
  • 25 25503 CORP Code Enforcement Program BSJ Ad 270x270 WAD FINAL
  • 25 25461 MEM Community BSJ 270x270 WAD FINAL Week1
International Code Council
International Code Council
International Code Council
International Code Council

Subscribe to the Building Safety Journal

Subscribe

Connect with Us

  • LinkedIn
  • Facebook
  • X
  • YouTube
  • Instagram

oneICC

  • International Code Council
  • ICC Evaluation Service
  • International Accreditation Service
  • General Code
  • S. K. Gosh Associates
  • ICC NTA
  • Alliance for National & Community Resilience
  • ICC Community Development
  • American Legal Publishing
  • Privacy Policy
  • Terms of Use
  • Contact Us
  • Accessibility Policy
6keF2e2M1-FG9DJemz9Xq_UilHkahmS6CRI_6VfitBk=.html