Skip to Main Content
Building Safety Journal Logo

Building Safety Journal - International Code Council

Main Menu

Menu

      • April, 2025 Articles
      • March, 2025 Articles
      • February, 2025 Articles
      • January, 2025 Articles
      • December, 2024 Articles
      • November, 2024 Articles
      • 2025 Articles
      • 2024 Articles
      • Deep Dives
      • Member News
      • Personal Perspectives
      • Quick Hits
      • Technical Topics
      • Press Releases
      • Sponsored Content
      • View All
      • Buildings, Construction, Architecture/Design
      • Fire, Wildland-Urban Interface
      • Plumbing, Mechanical, Fuel Gas, Pools/Spas
      • Energy, Solar, Green, Sustainability
      • Disaster Preparedness, Mitigation, Resiliency
  • Subscribe
    • ICC Family of Solutions
    • ICCSafe
    • myICC
    • Digital Codes
    • cdpACCESS
    • Store
    • Support

Join today!

Keep up-to-date on crucial industry news, innovative training and expert technical advice with a free subscription to the award-winning Building Safety Journal.

Subscribe

Sign In or Register Here

Provide your email address
Provide your password
Answer the math challenge
Please enter your e-mail address below. We will email you a link to reset your password.
Provide your email address
Answer the math challenge
To complete your registration, please verify your email address.
Answer the math challenge

We have emailed the address you provided. Please click the link in the email to confirm your email address.

Your account has been marked for password reset. Please change your password.
Provide your new password
Verify your new password
Answer the math challenge 6 plus three

Only registered ICC members have access to this article at this time.

Explore all the benefits that ICC Membership has to offer and become a member today to gain access to this exciting content.

If you're already an ICC member Sign In Now.

Can We Help?

  • Reset My Password
  • I Need More Help

Application of overstrength factor: How deep does it go?

January 6th, 2020
by S.K. Ghosh, Kirsten Zeydel
  • Technical Topics

When your columns are required to be designed for load combinations with overstrength, do you also need to design the foundation supporting those columns for amplified forces? Let’s find out from the following question we received recently and the response we provided.

Q. My understanding is the code does not require foundations (only connections where applicable) to be designed for the overstrength factor (uplift and bearing). I am specifically referring to foundation uplift on a column supporting a discontinuous system. Is this correct?

A. Your understanding is correct, but for one exception in ASCE 7-10, 7-16 Section 12.2.5.2, Cantilever Column Systems. The second paragraph of Section 12.2.5.2 reads:

Foundation and other elements used to provide overturning resistance at the base of cantilever column elements shall be designed to resist the seismic load effects, including overstrength of Section 12.4.3.

Please also note the Exception to 2018 International Building Code Section 1810.3.8.3.2, Seismic Reinforcement in Seismic Design Category C, and the Exception to Section 1810.3.8.3.3, Seismic Reinforcement in Seismic Design Categories D through F. Both exceptions allow Seismic Design Category B detailing in higher Seismic Design Category spirally reinforced precast prestressed piles, if the design loads transmitted from the superstructure to the foundation are amplified by the applicable overstrength factor.

The 2016 California Building Code has made the following modification to ASCE 7-10 Section 12.13.1, [Foundation] Design Basis, in Section 1616.10.14, applicable to community colleges in California and in Section 1616A.1.16, applicable to hospitals and schools in California:

1616.10.14, 1616A.1.16 ASCE 7, Section 12.13.1. Modify ASCE 7 Section 12.13.1 by adding Section 12.13.1.1 as follows:

12.13.1.1 Foundations and superstructure-to-foundation connections. The foundation shall be capable of transmitting the design base shear and the overturning forces from the structure into the supporting soil. Stability against overturning and sliding shall be in accordance with Section 1605.1.1.

In addition, the foundation and the connection of the superstructure elements to the foundation shall have the strength to resist, in addition to gravity loads, the lesser of the following seismic loads:

    1. The strength of the superstructure elements.
    2. The maximum forces that can be delivered to the foundation in a fully yielded structural system.
    3. Forces from the load combinations with over-strength factor in accordance with ASCE 7 Section 12.4.3.2.

Exceptions:

    1. Where referenced standards specify the use of higher design loads.
    2. When it can be demonstrated that inelastic deformation of the foundation and super-structure-to-foundation connection will not result in a weak story or cause collapse of the structure.
    3. Where seismic force-resisting system consists of light-framed walls with shear panels, unless the reference standard specifies the use of higher design loads.

Where the computation of the seismic overturning moment is by the equivalent lateral-force method or the modal analysis method, reduction in overturning moment permitted by Section 12.13.4 of ASCE 7 may be used.

Where moment resistance is assumed at the base of the superstructure elements, the rotation and flexural deformation of the foundation as well as deformation of the superstructure-to-foundation connection shall be considered in the drift and deformation compatibility analyses.

We feel that the modifications could have been written more clearly, and our suggestion would be to simply go by Item #3 and not worry about the other two. That way, if one or both of the other items produce smaller values, we are conservative. If one or both of the other two items produce larger values, you are still in compliance with the requirement.

Finally, in Chapter 16A of the 2016 California Building Code, the Office of Statewide Health Planning and Development and the Division of the State Architect have made the following addition in Section 1605A.1.1, Stability:

When using allowable stress design, factor of safety for soil bearing values shall not be less than the overstrength factor of the structures supported.

The above modification is applicable to schools and hospitals in California only.

About the Author
S.K. Ghosh
Dr. S.K. Ghosh, Ph.D., is known internationally for his work in earthquake engineering. He has influenced seismic design provisions in the United States for many years by serving on or chairing numerous committees and advisory panels. He specializes in the analysis and design, including wind and earthquake resistant design, of reinforced and prestressed concrete structures. Dr. Ghosh is active on many national technical committees and is a fellow of ASCE, SEI, ACI, and PCI. He is a member of ACI Committee 318, Standard Building Code, and the ASCE 7 Standard Committee (Minimum Design Loads for Buildings and Other Structures). He is a former member of the Boards of Direction of the Building Seismic Safety Council, the American Concrete Institute, and the Earthquake Engineering Research Institute. In addition to authoring many publications in the area of structural design, he has investigated and reported on structural performance in recent earthquakes.
Kirsten Zeydel, S.E., is a structural consultant with S.K. Ghosh Associates LLC, the structural engineering manager for EIG Building Components, and the president of ZO Consulting. She is a licensed structural engineer, based in Southern California, with more than 16 years of experience in the design of cold-formed steel framing. She has led the structural design of both exterior and interior non-load-bearing cold-formed framing in addition to the structural design of load-bearing cold-formed steel buildings up to five stories in height. She has successfully taken many projects through the rigorous California Office of Statewide Health Planning and Development and the California Division of the State Architect. In practice, Kirsten Zeydel specializes in the design and coordination of exterior building “skins” in order to ensure they perform as expected during earthquakes and wind events.
Submissions
Check out upcoming BSJ topics and send us articles for consideration:
Or send by email

Want to advertise in the BSJ?
Click Here

Share on Facebook
Facebook
Tweet about this on Twitter
Twitter
Share on LinkedIn
Linkedin

  • 25 24731 BSM BSJ Website 270x270 WAD FINAL
  • 25 24651 TRN WDS BSJ BSJW WAD 270x270 FINAL a
  • 24 24393 TRN Learn Live Subscription BSJ AD 270x270 FINAL c
  • tile 3
  • 25 24699 PD TRN SKGA Sub Plan BSJ WAD FINAL 270 x 270 2
International Code Council
International Code Council
International Code Council
International Code Council

Subscribe to the Building Safety Journal

Subscribe

Connect with Us

  • LinkedIn
  • Facebook
  • X
  • YouTube
  • Instagram

ICC Family of Solutions

  • Privacy Policy
  • Terms of Use
  • Contact Us
  • Accessibility Policy
UC7UwcJXFMT1gJdG_bbRj9mmfxadBn6klvXQsOAL2ng=.html