Skip to Main Content
Building Safety Journal Logo

Building Safety Journal - International Code Council

Main Menu

Menu

      • April, 2025 Articles
      • March, 2025 Articles
      • February, 2025 Articles
      • January, 2025 Articles
      • December, 2024 Articles
      • November, 2024 Articles
      • 2025 Articles
      • 2024 Articles
      • Deep Dives
      • Member News
      • Personal Perspectives
      • Quick Hits
      • Technical Topics
      • Press Releases
      • Sponsored Content
      • View All
      • Buildings, Construction, Architecture/Design
      • Fire, Wildland-Urban Interface
      • Plumbing, Mechanical, Fuel Gas, Pools/Spas
      • Energy, Solar, Green, Sustainability
      • Disaster Preparedness, Mitigation, Resiliency
  • Subscribe
    • ICC Family of Solutions
    • ICCSafe
    • myICC
    • Digital Codes
    • cdpACCESS
    • Store
    • Support

Join today!

Keep up-to-date on crucial industry news, innovative training and expert technical advice with a free subscription to the award-winning Building Safety Journal.

Subscribe

Sign In or Register Here

Provide your email address
Provide your password
Answer the math challenge
Please enter your e-mail address below. We will email you a link to reset your password.
Provide your email address
Answer the math challenge
To complete your registration, please verify your email address.
Answer the math challenge

We have emailed the address you provided. Please click the link in the email to confirm your email address.

Your account has been marked for password reset. Please change your password.
Provide your new password
Verify your new password
Answer the math challenge 4 plus six

Only registered ICC members have access to this article at this time.

Explore all the benefits that ICC Membership has to offer and become a member today to gain access to this exciting content.

If you're already an ICC member Sign In Now.

Can We Help?

  • Reset My Password
  • I Need More Help

CodeNotes: Installation of Air Admittance Valves

This CodeNotes resource provides information on the correct installation of air admittance valves based on the 2021 International Codes.

September 12th, 2023
by Jim Cika, Gary Gauthier, Charles Lee Clifton
  • Technical Topics

This edition of CodeNotes —Installation of Air Admittance Valves — is based on the 2021 International Plumbing Code® and 2021 International Residential Code®. 

Introduction

Installation of Air Admittance Valves

The air admittance valve (AAV) is a device designed to allow air to enter the drainage system to balance the pressure and prevent siphonage of the water trap when negative pressure develops in the system. In this way, it is used on individual vents, branch vents and circuit vents in lieu of terminating vents to the exterior of the structure. Stack vents and vent stacks are permitted to terminate to a stack-type AAV. The exception is for stack vents or vent stacks that serve drainage stacks exceeding six branch intervals.

Because the AAV will not provide relief of positive pressures, there are certain installation requirements specified in the IPC to relieve positive pressure. The one open pipe vent required on every building drainage system in section 918.7 of the IPC and section P3114.7 of the IRC, Vent Required, and section 904.1 of the IPC and section P3102.1 of the IRC, Required Vent Extension, mandates that at least one vent pipe shall extend to the outdoors to relieve the system’s positive pressure. See Figure 1. Section 918.3.1, Horizontal Branches of the IPC, contains measures for pressure relief by requiring the installation of a relief vent where the horizontal branch is located more than four branch intervals from the top of the stack. This would not apply in the IRC.

An AAV without an engineered design shall not be utilized to vent sumps or tanks of any type. Figure 2 shows an example of one manufacturer’s engineered design for use of an AAV on a sump.

Figure 1
Figure 1

An AAV has one moving part, a seal, which must be maintained a safe distance above the drain served. In the event of a drain stoppage, the seal may become inoperable or operate improperly if waste is permitted to rise into the AAV assembly.

The AAV need not extend above the flood-level rim of the fixture served because in the event of a drain blockage, the device will trap air between it and the rising waste, thereby protecting the device from contamination. The illustration of the AAV in Figure 3 is shown in the closed position. The valve is designed to close and seal under zero or positive pressure.

 

Figure 2
Figure 2
Figure 3
Figure 3

AAV in Branch Applications (ASSE 1051)

In the IPC, AAVs shall be installed in accordance with the requirements of section 918 and the manufacturer’s instructions. The AAVs shall be installed after the DWV testing required by Section 312.2 or 312.3 has been performed. The IRC requires AAVs be installed in accordance with section P3114 and the manufacturer’s instruction. The AAVs shall be installed after the DWV testing required by Section P2503.5.1 or P2503.5.2 has been performed.

Individual and branch-type AAVs shall not be located not less than 4 inches (102 mm) above the horizontal branch drain or fixture drain being vented. See Figure 4, Examples 1, 2 and 3.

AAVs shall be accessible, should replacement be required. Such valves shall be installed in a location that allows air to enter the valve. Locating the valve in a sink or vanity cabinet is accessible. For in-wall installation, use a recess box/grill combination or access grill. See Figure 5. The AAV shall be installed not less than 6 inches (152 mm) above the insulation material. See Figure 6.

Example 1
Example 1
Example 2
Example 2
Example 3
Example 3

AAV in a Stack Application (ASSE 1050)

The stack-type AAV shall be located not less than 6 inches (152 mm) above the flood-level rim of the highest fixture being vented. The AAV shall be located within the maximum developed length permitted for the vent. See Figure 7.

AAVs shall be accessible, should replacement be required. Such valves shall be installed in a location that allows air to enter the valve. The AAV shall be installed not less than 6 inches (152 mm) above insulation materials that may block air inlets or otherwise impair the operation of the device.

Figure 5
Figure 5
Figure 6
Figure 6
Figure 7
Figure 7

Plumber Installation Tips

  • Always check the manufacturer’s installation instructions for additional recommendations and warranty requirements.
  • Most manufacturers recommend that you not install the AAV’s until after the drainage and waste systems have been roughed and tested.
  • Teflon tape is usually what manufacturers prefer on the valve thread connection. The use of primer, solvent cement or pipe dope will void most manufacture warranties. Always check the manufacturer’s installation instructions before installing.
  • Pop-up drainage linkage could interfere with the installation of the AAV. Offset drain waste to avoid any conflict. See Figures 8 & 9
Figure 8
Figure 8
Figure 9
Figure 9

In summary, the installation of AAVs must conform to the requirements of section 918 of the IPC, Air Admittance Valves, or section P3113 of the IRC, Vent Pipe Sizing, and the manufacturer’s instruction. Where differences occur between the provisions of the code and the manufacturer instructions, the most restrictive provisions must apply.

To learn more about the code requirements for the installation of AAVs, please refer to the 2021 IPC Code and Commentary, and the 2018 IRC Code and Commentary.

About the Author
Jim Cika
Jim Cika, director, PMG technical resources for the International Code Council, where he serves as a subject matter expert to the plumbing, mechanical, and fuel gas codes. He represents ICC in federal and state coalitions, task forces, committees, and councils where expertise in I-Code subjects is required. Cika has more than 20 years of experience in the manufacturing and construction industry where he has served as chief technical expert for regulatory, product standards, building code and product engineering matters.
Gary Gauthier
Gary has over 40 years of experience working within the Construction and Plumbing Industry. He is a seasoned Construction Project Manager as well as a Licensed Master Plumber in Massachusetts, New Hampshire, Maine and Vermont. In addition, Gary holds an Unrestricted Construction Supervisor’s License (CSL) within the state of Massachusetts and completely understands the significance of code correlation. Lastly, while working with the International Code Council, he is currently an Adult Educational Master Plumbing & Fuel Gas Instructor and Continuing Education Instructor in the Commonwealth of Massachusetts. Member of the International Code Council PMG Team responsible for developing, coordinating, directing and implementing programs to ensure the successful completion of the Government Relations goals and objectives as they apply to the International Plumbing Code, International Mechanical Code, International Fuel Gas Code, International Swimming Pool and Spa Code, and the International Private Sewage Disposal Code (and related services and programs of the International Code Council).
Charles Lee Clifton
Charles Lee Clifton, retired senior director of plumbing, mechanical and fuel gas resources for the International Code Council, has more than 45 years of experience in the plumbing, mechanical and fuel gas industry. His career began as a second-generation plumber, working for his father at Clifton Plumbing Inc., in Tampa, Florida. He retired from the city of Los Angeles in 2007 as a principal inspector after 21 years of service. He retired from the International Code Council after 13 years of service.
Submissions
Check out upcoming BSJ topics and send us articles for consideration:
Or send by email

Want to advertise in the BSJ?
Click Here

Share on Facebook
Facebook
Tweet about this on Twitter
Twitter
Share on LinkedIn
Linkedin

  • 25 24862 MTS CLE BSJ WAD 270X270 FINAL
  • 25 24731 BSM BSJ Website 270x270 WAD FINAL
  • 25 24651 TRN WDS BSJ BSJW WAD 270x270 FINAL a
  • tile 3
  • 25 24699 PD TRN SKGA Sub Plan BSJ WAD FINAL 270 x 270 2
International Code Council
International Code Council
International Code Council
International Code Council

Subscribe to the Building Safety Journal

Subscribe

Connect with Us

  • LinkedIn
  • Facebook
  • X
  • YouTube
  • Instagram

ICC Family of Solutions

  • Privacy Policy
  • Terms of Use
  • Contact Us
  • Accessibility Policy
FOguGMM0vGZ5c96DdbgF7gCavqW7_QF2vyNeCj2GUx0=.html