Skip to Main Content
Building Safety Journal Logo

Building Safety Journal - International Code Council

Main Menu

Menu

      • April, 2025 Articles
      • March, 2025 Articles
      • February, 2025 Articles
      • January, 2025 Articles
      • December, 2024 Articles
      • November, 2024 Articles
      • 2025 Articles
      • 2024 Articles
      • Deep Dives
      • Member News
      • Personal Perspectives
      • Quick Hits
      • Technical Topics
      • Press Releases
      • Sponsored Content
      • View All
      • Buildings, Construction, Architecture/Design
      • Fire, Wildland-Urban Interface
      • Plumbing, Mechanical, Fuel Gas, Pools/Spas
      • Energy, Solar, Green, Sustainability
      • Disaster Preparedness, Mitigation, Resiliency
  • Subscribe
    • ICC Family of Solutions
    • ICCSafe
    • myICC
    • Digital Codes
    • cdpACCESS
    • Store
    • Support

Join today!

Keep up-to-date on crucial industry news, innovative training and expert technical advice with a free subscription to the award-winning Building Safety Journal.

Subscribe

Sign In or Register Here

Provide your email address
Provide your password
Answer the math challenge
Please enter your e-mail address below. We will email you a link to reset your password.
Provide your email address
Answer the math challenge
To complete your registration, please verify your email address.
Answer the math challenge

We have emailed the address you provided. Please click the link in the email to confirm your email address.

Your account has been marked for password reset. Please change your password.
Provide your new password
Verify your new password
Answer the math challenge 9 minus zero

Only registered ICC members have access to this article at this time.

Explore all the benefits that ICC Membership has to offer and become a member today to gain access to this exciting content.

If you're already an ICC member Sign In Now.

Can We Help?

  • Reset My Password
  • I Need More Help

IECC Q&A: Switches and lighting occupancy sensors in storage rooms

January 27th, 2020
by Michelle Britt
  • Technical Topics

In this column, we will address some of the typical questions asked of our technical support team. As always, code opinions issued by International Code Council staff are based on published Code Council codes and do not include local, state or federal codes; policies; or amendments. This opinion does not imply approval of an equivalency, specific product, specific design or specific installation and cannot be published in any form implying such approval by the International Code Council. As this opinion is only advisory, the final decision is the responsibility of the designated authority charged with the administration and enforcement of this code. All code citations reference the 2018 International Energy Conservation Code (IECC) unless otherwise specified.

 


 

Switches and lighting occupancy sensors in storage rooms

 

Q: The situation is a stock-storage room for a retail establishment. Section C405.2.1.1 of the 2018 International Energy Conservation Code (IECC) requires that occupant sensors need manual control. Our client wants a ceiling-mounted sensor only with no wall switch override. Section C405.2.1.1, Condition 3, says a manual control is required. Is it acceptable for this area to be controlled only by a ceiling occupancy sensor (on and off) without a manual control switch on the wall? The reality is the employees are likely not to use the switch and the ceiling sensor would control the lights 99 percent of the time.

A: No, Section C405.2.1.1 provides no exceptions for the manual control requirement. Occupant sensors are automatic control devices that detect occupancy and adjust lights in response to the presence or absence of people in the space. Most devices can be calibrated for length-of-time delay between the last detected occupancy and extinguishing of the lights. Section C405.2.1.1, Condition 1, specifically requires that this time delay cannot be longer than 20 minutes, the shorter the time delay setting, the greater the energy savings, as the lights will spend more time “off.”

Occupant sensors save energy by turning lights off automatically. In most spaces such as the stock/storage room referenced, occupant sensors must be configured to turn on automatically to not more than 50-percent power (Condition 2), and an accessible switch must be provided to bring lights to full output. Turning lights on automatically never saves energy because there are many instances where a user would not choose to turn lights on. For this reason, full automatic-on is only permitted in “public corridors, stairways, restrooms, primary building entrance areas and lobbies and areas where manual-on operation would endanger the safety or security of the room or building occupants” (see the exception to Section C405.2.1.1, Condition 2). Remember that even in these spaces, an accessible manual switch must still be provided to allow occupants to turn lights off where they choose (C405.2.1.1, Condition 3).

About the Author
Michelle Britt
Michelle Britt is the former director of energy programs at the International Code Council. She has more than 15 years of experience impacting building energy use and broader sustainability and has served national, state and local governments; industry; and non-profits across the U.S. and the Pacific. Her broad background in land use and transportation planning and environmental impact analysis brings a holistic approach to her work in building energy. Previously, she was a partner with the Britt/Makela Group and a senior research scientist with the Pacific Northwest National Laboratory. She holds a bachelor’s degree in environmental studies and a master’s degree in architecture.
Submissions
Check out upcoming BSJ topics and send us articles for consideration:
Or send by email

Want to advertise in the BSJ?
Click Here

Share on Facebook
Facebook
Tweet about this on Twitter
Twitter
Share on LinkedIn
Linkedin

  • 25 24862 MTS CLE BSJ WAD 270X270 FINAL
  • 25 24731 BSM BSJ Website 270x270 WAD FINAL
  • 25 24651 TRN WDS BSJ BSJW WAD 270x270 FINAL a
  • tile 3
  • 25 24699 PD TRN SKGA Sub Plan BSJ WAD FINAL 270 x 270 2
International Code Council
International Code Council
International Code Council
International Code Council

Subscribe to the Building Safety Journal

Subscribe

Connect with Us

  • LinkedIn
  • Facebook
  • X
  • YouTube
  • Instagram

ICC Family of Solutions

  • Privacy Policy
  • Terms of Use
  • Contact Us
  • Accessibility Policy
8hal3lS3DD2dfN0krpjcKEG6S_E4LzXwiMSKIoxutQ4=.html